Energy Saving Analysis of Variable Primary Flow System with Screw Chiller

Authors: Yung-Chung Chang, Pin-Cheng Chieng, Jyun-Ting Lu, Tien-Shun Chan, Ching-Liang Chen, Cheng-Wen Lee

This paper focuses on energy-saving operation and use of the variable primary flow (VPF) of a central air-conditioning system chiller, by means of regression analysis to determine the relationship equation of chiller power consumption and cooled water flow rate, cooled water supply temperature, cooling water return temperature, and partial load, and the relationship equation of the cooled water pump power consumption and the cooled water flow rate. Take the relationship equations as basis to identify the power consumption change curve of loads in different flow rates, and calculate the most energy-saving cooled water flow rate of the chiller and the cooled water pump in various loads.

Comments: 18 Pages.

Download: PDF

Submission history

[v1] 2014-05-07 04:31:46

Unique-IP document downloads: 895 times

Vixra.org is a pre-print repository rather than a journal. Articles hosted may not yet have been verified by peer-review and should be treated as preliminary. In particular, anything that appears to include financial or legal advice or proposed medical treatments should be treated with due caution. Vixra.org will not be responsible for any consequences of actions that result from any form of use of any documents on this website.